145(126)kv Gas-insulated Metal-enclosed Switchgear(GIS)

145(126)kv Gas-insulated Metal-enclosed Switchgear(GIS)
Product Detailed
126(145)KV GIS has high safety and reliability,easy maintenance and repair,low noise,short installation period .

ZF10-126G(L)/ T3150-40 Gas-insulated Metal-enclosed Switchgear

This product is developed on the basis of research on GIS for many years and absorption of domestic and foreign GCB technology.

Feature:

 1,Epoch-making compact:volume contracted GIS is merely 40% of common deflection phase type GIS.

2,Minimum volume,light weight and earthquake resistant:it is product of minimum volume among similar domestic GIS compartment units,standard compartment width is only 1.2 to 1.5m;casing and conductor adopt aluminum alloy material ,which features corrosion resistant,light weight and good earthquake resistant performance ,standard compartment weight is about 2 to 4 MT.

3,Strong breaking capacity:circuit breaker adopt self-energy arc extinction principle,has very high short circuit breaking and closing capacity,charging current of breaking and closing circuit has no re-strike and re-arcing phenomena.electric life reaches 16 times;isolating switch could meet the requirement of closing bus transfer current and bus charging current ,earth switch could meet the requirement of closing short circuit current and closing induction current;

Rated voltage

126kv(145kv)

Rated frequency

50Hz(60)

Rated current

2000,2500,3150.

Rated short time withatand current

40KA/4S

Rated peak withstand current

100KA

Rated short time power frequency withatand voltage

To earth:230kv

Between fractures:230+73kv

Phase to phase:230+115kv

Rated lightning impulse withatand voltage

To earth :550kv

Between fracture:550+103kv

SF6 gas pressure(20) rated value/alarm value/locking value

Compartment:0.6/0.55/0.5Mpa

SF6 gas pressure (20) rated value/alarm value

Other compartment:0.5/0.4Mpa

SF6 gas water content(volume ratio) control value/permissible value

Circuit breaker compartment:

150/300ppm

Other compartment:<250/500ppm

Yearly leakage rate of SF6 gas

<1%

Control circuit and auxiliary circuit voltage,

DC110 or 220v,AC 220 or 380v